Need help deciding which solution is right for you? Contact sales on 020 3744 9539
Metz Connect BMT-TO4
The Metz Connect BMT-TO4 BACnet MS/TP IO module with 4 digital triac outputs was developed for decentralized switching tasks.
It is suitable for switching electrical components, such as relays, contactors, HLK valves, etc. The outputs can be switched by means of standard objects via a BACnet client. In addition, the outputs can be overridden manually by means of switches on the device.
Protocols: BACnet MSTP
Product Description
The module is addressed and the baud rate is set by means of two address switches on the front. Suitable for decentralized mounting on DIN TH35 rail according to IEC 60715 in electrical distribution cabinets.
BACnet MS/TP
00 to F9
RS485 (two-wire bus)
9600 to 115200 bit/s
24 V AC/DC +/- 10 % (SELV)
100 mA (AC) / 40 mA (DC)
100 %
4 digital outputs (triac)
24 V AC up to max. 250 V AC
BACnet MS/TP
00 to F9
RS485 (two-wire bus)
9600 to 115200 bit/s
24 V AC/DC +/- 10 % (SELV)
100 mA (AC) / 40 mA (DC)
100 %
4 digital outputs (triac)
24 V AC up to max. 250 V AC
0.5 A / output
0.8 A (less than 30 s)
10 A (less than 20 ms)
Green, red and yellow LED
35 x 69.3 x 60 mm
95 g
-5 °C to 55 °C
-20 °C to 70 °C
IP40 / IP20