Analogue Input and Output

2 digital inputs, 1 Analogue input 0-10V, 1 Analogue output 0-10V

Key Features
  • 1 analogue input to detect a voltage direct-current signal in between 0 and 10 Vdc
  • 1 analogue output to detect a voltage direct-current signal in between 0 and 10 Vdc
  • 1 Digital input
  • 1 NTC Input
  • 12-24 Vdc/Vac supply
  • RF power amplifier: 10 mW
  • Routing function
  • External antenna
ZR-AIAO-EM belongs to ZB-Connection devices family. It features a sensor/actuator provided with one 0-10Vdc analogue input, one NTC input, one digital input and one 0-10Vdc analogue output. Its task is to acquire inputs and send the data it acquires and generates to a compatible Gateway at regular intervals. The digital inputs control up to two pulse counter. The device requires a continuous 12/24 Vdc (or 12/24 Vac) power supply. For network purposes, it is a Router i.e. it has the active function of maintaining radio traffic from and to other similar devices and it can also act as a parent device for battery-powered nodes of the same family.
Technical Characteristics


General characteristics
Chip Ember EM2420
Compatible IEEE 802.15.4
Stack EmberZnet 3.5.x (ZigBee PRO)
Device address settable via internal dip-switch
Wall mounting with screws
Cable gland: PG9
RF characteristics
Frequency: 2405 MHz ÷ 2480 MHz
Modulation: DSSS
Nominal transmission power: 10mW (10 dBm)
Reception sensitivity: -97 dBm
External antenna gain: 5,5 dB
Coverage outdoor/indoor: 200m/50m
Power Supply
24Vcc/Vca (±10%); 100mA; 50/60Hz
Analouge input
0-10 Vdc
Reading accuracy ±1%
Input impedence: 5 KOhm
Analouge output
0-10 Vdc
Reading precision: ± 2%
Output with PWM at 10KHz
NTC input
NTC Sensor 103AT Type (R25 = 10 KOhm; Beta = 3435K)
Measurement range -50°C ÷ +110°C
Reading resolution 0,1°C
Reading accuracy ±0,5°C
Digital inputs
Electronic type not insulated inputs for clean contact.
Short circuit current 0,01mA. Use self-cleaning contacts.
Pull out terminals (3,81 mm pitch)
Environment parameters Operating temperature: -10 ÷ +60°C; <80% U.R. not condensing
Storage temperature: -20 ÷ +70°C; <80% U.R. not condensing
Degree of protection: IP 55
Compliant with 2006/95/EEC, 89/336/EEC, 99/5/EEC directives Reference Norms ETSI EN 300 328: Radio Compatibility for digitals wide band transmissions ETSI EN 301 489: Radio Compatibility
EN 61000-6-2: Electromagnetic Compatibility – Emissions
EN 61000-6-3: Electromagnetic Compatibility – Immunity
EN 60950-1: Electric Safety