.Mix 18-IP 2019-02-07T10:07:55+00:00

iSMA-B-Mix-18-IP

iSMA

In order to ensure high versatility and price performance the MIX18-IP module has been equipped with the most commonly used types of I/O in building automation (MIX of all types of I/O in one unit). The module has 5xUI (Universal Inputs), 5xDI(Digital Inputs), 4xAO (Analog Outputs) and 4xDO (Digital Outputs).

GET A QUOTE

The module is factory-equipped with the two most popular open communication protocols: Modbus TCP/IP and BACnet IP, which are selected using DIP switches.

The Mix 18-IP has a built-in Modbus Gateway TCP/IP to Modbus ASCII/RTU, enabling you to connect additional modules/devices that communicate via Modbus RS485.

Addressing the modules is done via rotary switches, which facilitates and accelerates the process of commissioning the system.

There is also a built-in mini USB that allows for initial configuration of the unit without a power supply.

Inputs & Outputs

5x universal inputs

All universal inputs are equipped with 16-bit converters, which support the following types of inputs:

  • Temperature inputs work with the following types of sensors: 10K3A1, 10K4A1, Carel 10K 20K6A1, 2.2K3A1, 3K3A1, 30K6A1, SIE1, TAC1, SAT1, Pt1000, Ni1000 For Pt1000 and Ni1000 used only resolution 16bit
  • Input voltage 0-10 V DC input resistance of 100 kW ± 0.1%, resolution 3 mV @ 12bit and 16bit 1 mV @
  • 0-20 mA current inputs
  • Inputs resistive 0-1000 kohm: resolution at 20 kohm 20 Ω @ 12bit and 16bit 1 Ω @
  • Inputs potential-free (dry contact)

5x digital inputs

  • Inputs potential-free (dry contact)
  • Fast pulse counter up to 100 Hz writing to the EEPROM

4x analog outputs

All analog outputs feature 12-bit ADC which provides a resolution of 10 mV and error of ± 0.5%. Supports the following types of outputs:

  • Output voltage 0-10 V DC max. 20 mA
  • PWM output: 0.01 Hz, 0.1 Hz, 1 Hz, 10 Hz, 100 Hz

4x digital outputs

Relay output (NO) max. 3 A, 230 V AC / 30 V DC

Communication

  • Interface RS485 half duplex
  • Up to 99 devices on the bus
  • Protocols: Modbus or BACnet
  • Baud rate: 2400 to 115200 bps

8 x Digital Inputs (4DI)

All universal inputs are equipped with 16-bit converters, which support the following types of inputs:

  • Temperature inputs work with the following types of sensors: 10K3A1, 10K4A1, Carel 10K 20K6A1, 2.2K3A1, 3K3A1, 30K6A1, SIE1, TAC1, SAT1, Pt1000, Ni1000 For Pt1000 and Ni1000 used only resolution 16bit
  • Input voltage 0-10 V DC input resistance of 100 kW ± 0.1%, resolution 3 mV @ 12bit and 16bit 1 mV @
  • 0-20 mA current inputs
  • Inputs resistive 0-1000 kohm: resolution at 20 kohm 20 Ω @ 12bit and 16bit 1 Ω @
  • Inputs potential-free (dry contact)

Housing

  • Dimension: 88x110x62 mm
  • Construction: plastic, self-extinguishing (PC/ABS)
  • DIN rail mounting (DIN EN 50022 norm)
  • Cooling: internal air circulation

Environment

  • Operating temperature: -10°C to 50°C
  • Storage temperature: -40°C to 85°C
  • Relative humidity: 5 to 95%, no condensation
  • Ingress Protection Rating: IP40 – for indoor installation

Platform

  • ARM Cortex-M3

Power supply

  • 24 C AC/DC

The datasheet for this product can be downloaded here in PDF format:

DATASHEET
We use cookies on this website, by continuing you consent to our use of them. For more information please read our Privacy Policy.
Holler Box